The 6ES7134-6HB00-0CA1 is an analog input module from Siemens’ SIMATIC ET 200SP series, specifically designed for high-precision temperature measurement using resistance temperature detectors (RTDs). Here’s a detailed description:
Basic Information
- Product Type Designation: AI 4xRTD HF, indicating 4 analog input channels for resistance temperature detectors (RTDs) with High Feature (HF) capabilities.
- Usable Base Units: Compatible with BU type A0.
- Color Code: CC11.
- Hardware Functional Status: From FS07 onwards.
- Firmware Version: Upgradable, allowing for future functionality enhancements.
Power Supply Characteristics
- Power Supply Voltage: Rated at 24V DC, with an allowable range of 19.2V DC to 28.8V DC. It includes reverse polarity protection.
- Current Consumption: Maximum current draw from the backplane bus is 60mA.
- Power Loss: Typical power consumption is 1.2W.
RTD Input Characteristics
- Number of Inputs: 4 (fully isolated channels with galvanic isolation between each channel and from the backplane bus).
- Supported RTD Types: Configurable per channel for Pt100, Pt200, Pt500, Pt1000 (platinum), and Ni100, Ni1000 (nickel) resistance thermometers.
- Measurement Ranges: Dependent on RTD type, typically spanning -200°C to +850°C for Pt100.
- Resolution: 16 bits (including sign bit), providing high-precision temperature readings.
- Accuracy: ±0.05% of measured value (typical) at 0°C to +100°C, with enhanced precision compared to standard modules.
- Wiring Options: Supports 2-wire, 3-wire, and 4-wire connections, with advanced lead resistance compensation for 3-wire and 4-wire configurations.
- Sampling Rate: 0.5kS/s (total for all channels).
Advanced Features
- Diagnostics: Comprehensive diagnostic capabilities including power supply monitoring, wire break detection in RTD circuits, short-circuit detection, and overrange/underrange conditions. Status is indicated via LEDs: green PWR-LED (power), green channel-status LEDs, red channel-diagnostic LEDs, and a green/red DIAG-LED (module diagnostics).
- Configuration: Channel-specific parameterization (RTD type, wiring type, measurement range, filtering) via TIA Portal; includes advanced linearization, scaling, and averaging functions.
- Isolation: 500V AC galvanic isolation between channels and from the backplane bus, ensuring robust performance in noisy industrial environments.
Configuration and Communication
- Supported by configuration tools including STEP 7 TIA Portal (from version V13 SP1), STEP 7 (from version V5.5), and PCS 7 (from version V8.1 SP1).
- Compatible with PROFIBUS and PROFINET fieldbuses, using GSDML V2.3 (PROFINET) and GSD files of revision 3 and 5 or higher (PROFIBUS).
Mechanical and Environmental Specifications
- Dimensions: 15mm width, 73mm height, 58mm depth.
- Weight: Approximately 30g.
- Operating Temperature: -30°C to 60°C when mounted horizontally; -30°C to 50°C when mounted vertically (with adjusted lower limits for FS07 and later).
- Mounting Altitude: Up to 5000m, with derating requirements for altitudes exceeding 2000m.
- Electromagnetic Compatibility (EMC): Complies with relevant IEC standards for industrial environments, ensuring reliable operation in harsh electrical conditions.